MaisonProduitsArmoire de système UPS intelligent modulaire en ligne haute puissance de 50 à 200 kW
  • 50-200kW online modular intelligent UPS
  • High-power online modular intelligent UPS
  • 50-200kW online modular intelligent UPS
  • High-power online modular intelligent UPS

Armoire de système UPS intelligent modulaire en ligne haute puissance de 50 à 200 kW

High power density, saving more than 10% of floor space compared with similar products in the industry.

High cost performance, supports battery design without a neutral wire (optional), and is friendly to lithium batteries.

Super strong environmental adaptability, comprehensive protection at the system level, board level and device level, ultimate reliability.

Large LCD touch screen, color graphic display, convenient operation and friendly human-machine interface.

High-integration PCB design enhances product assemblability and reduces the rate of human failure.

Optimize the heat dissipation layout, with a higher design margin. If a single fan fails, it can still carry 70% of the load.

Introduction

Paramètres

Télécharger

Online Modular Intelligent UPS:

This High-Power Online Modular Intelligent UPS product features a high power density and saves over 10% of floor space compared to similar products in the industry, providing users with a more space-saving solution. Meanwhile, it features high cost performance, supports battery centerless design (optional), and can be well adapted to lithium batteries, meeting various application requirements. The product also features outstanding environmental adaptability, with comprehensive protection designs at the system level, board level and device level, ensuring ultimate reliability.

Online Modular Intelligent UPS Key Advantage:

  1. High power and stability

With a rated capacity of 200KVA/200kW, it is suitable for high-power loads, supporting input voltages of 380/400/415VAC (line voltage) and 220/230/240VAC (phase voltage), with a frequency of 50/60Hz, a power factor >0.99, and an electrical current accuracy THDi<2%.

  1. Wide voltage and frequency adaptability

Supports an input voltage range of 304-478VAC. When the load drops from 100% to 50%, the voltage decays linearly. It can accept a frequency range of 40 to 70Hz and adapt to different power environments.

  1. Precise output and low harmonic distortion

The output voltages are 380/400/415VAC (line voltage) and 220/230/240VAC (phase voltage), the output power factor is 1, and the voltage accuracy is ±1.0%. The total harmonic distortion (THDu) is less than 1% under linear load and less than 5% under nonlinear load.

  1. Rapid dynamic response and recovery

The dynamic response time is less than 5% (20%-80%-20% load step response), and the dynamic recovery time is less than 20ms (0%-100%-0% load step recovery), ensuring a rapid and stable recovery when the load changes.

  1. Overload protection function

It features multiple overload protections: bypasses after 1 hour at 110% load, bypasses after 10 minutes at 125% load, bypasses after 1 minute at 150% load, and automatically bypasses after 200ms when the load exceeds 150%.

  1. Precise frequency control and phase stability

The frequency accuracy is 0.10%, supporting a frequency tracking range from ±0.5Hz to ±5Hz, with a default of ±3Hz. The tracking rate is from 0.5Hz/S to 3Hz/S, with a default of 0.5Hz/S. The three-phase phase accuracy is 120°±0.5°, ensuring stable output.

Online Modular Intelligent UPS Application

UPS is widely used across various industries and sectors, including government, finance, telecommunications, education, transportation, meteorology, broadcasting, taxation, healthcare, and energy and power.

1.Government: UPS systems are critical in ensuring the uninterrupted operation of government networks, emergency services, and data centers. During power outages, they help maintain essential services such as public safety communication and disaster management systems.
2.Finance: In the finance sector, UPS provides backup power for bank branches, trading platforms, and ATMs, safeguarding sensitive financial transactions and data during power disruptions.
3.Telecommunications: UPS is crucial for telecom networks, ensuring that communication services, including mobile networks and the internet, remain operational even during electrical failures.
4.Healthcare: In healthcare facilities, UPS ensures that life-saving medical equipment such as ventilators, heart monitors, and surgical systems continue to function during power outages, preventing potential health risks.
5.Education: UPS is used in schools, universities, and research centers to protect computers, servers, and online learning systems, minimizing disruptions in educational services.
6.Energy and Power: In the energy sector, UPS helps maintain power plants, substations, and grid control systems, ensuring stability and reliability of the electricity supply during unforeseen power interruptions.
7.Meteorology: UPS systems provide critical backup power for weather stations and forecasting systems, ensuring the continuous monitoring and prediction of weather conditions without interruption.

In these industries, UPS plays a vital role in ensuring operational continuity and preventing data loss or system failure during power outages.

Modèle AC200/50
Capacité 200KVA/200kW
Entrée de la route principale Câblage d'entrée Phase 3 + ligne N + PE
Tension d'entrée 380/400/415VAC (tension de ligne) 220/230/240VAC (tension de phase)
Fréquence d'entrée 50/60 Hz
Facteur de puissance >0,99
Taux de distorsion actuel THDi<2%(100% linear load)
Plage de tension 304-478 VCA (tension de ligne) à pleine charge ; La charge de 304 à 228 VCA (tension de ligne) est réduite linéairement de 100% à 50%
Gamme de fréquences 40-70 Hz
Batterie Tension de la batterie Batterie à trois fils : ± 240 V CC (30 à 50 cellules peuvent être définies)
Deux fils de batterie en option : 480 VDC (30 à 50 cellules peuvent être définies)
Puissance de charge Puissance active maximale 20%*
Précision de la tension de charge ±1%
By-pass Tension de dérivation 380/400/415 VCA (tension de ligne) ; 220/230/240 VCA (tension de phase)
Plage de tension Paramétrable. La plage par défaut est de -20% à +15%. Limites supérieures : +10%, +15%, +20%, +25% ; Limites inférieures : -10%, -15%, -20%, -30%, -40%.
Capacité de surcharge

125%, long-term operation 125%< load <130%, no less than 10 minute

130%< load <150%, not less than 1 minutes, >150%,300 ms

Sortir Tension de sortie nominale 380/400/415 VCA (tension de ligne) ; 220/230/240 VCA (tension de phase)
Fréquence nominale 50/60 Hz
Facteur de puissance de sortie 1
Précision de la tension ±1,0%
Réponse dynamique de sortie <5% (20%-80% -20% charge par paliers)
Temps de récupération dynamique <20 ms (0%-100% -0% charge par paliers)
Distorsion harmonique totale de sortie (THDu) <1% (charge linéaire), <5% (charge non linéaire)
Surcharge de l'onduleur 110%, passage en mode bypass après 1 heure ; 125%, passage en mode bypass après 10 minutes ; 150%, passage en mode bypass après 1 minute ; >150%, passage en mode bypass après 200 ms
Précision de fréquence 0.10%
Portée de suivi Réglable : ±0,5 Hz-±5 Hz, par défaut ±3 Hz
Taux de suivi Réglable : 0,5 Hz/s-3 Hz/s, par défaut 0,5 Hz/s
Rapport de pointe 3:1
Précision de phase triphasée 120°±0,5°
Système Efficacité du système Main road mode ≥97%; Battery mode >97%
Afficher Écran tactile couleur LCD+LED+7 pouces
Règles de sécurité IEC62040-1, IEC60950-1
CEM IEC62040-2 ; IEC61000-4-2 (DES) ; IEC61000-4-3 (RS) ; IEC61000-4-4 (EFT) ; IEC61000-4-5 (Surtension)
Degré de protection IP20
Configuration standard USB, RS232, RS485, carte à contact sec, démarrage à froid de la batterie
Sélectionner les accessoires Carte SNMP, carte à contact sec étendue, composant parallèle, LBS, APP/WiFi/Bluetooth
Wiring method Front-entry cable, or front-entry cable can be selected as an option
Environnement de travail 0-40℃ (température de fonctionnement) -25℃ à 70℃ (température de stockage) 0-95% (sans condensation)
Bruit (dB)(1 mètre) 68dB @ 100% load, 65dB @ 45% load
Taille Armoire (L*P*H) mm 600*750*1600
Module (L*P*H) mm 440*475*140